GE RUGBY

Delivering A Tailored Electrical Installation
Delivering a bespoke electrical installation as part of our ongoing works at GE Rugby, supporting operational efficiency and safety through tailored power solutions. Recent Installations Include: 3-phase, 6-way Hager fuse board with 125A main switch, supply via 25mm 4-core SWA cable with 16mm earth, fed from mezzanine distribution board, three 40A 3-phase MCBs wired to enclosed units for controlled contractor access. Each enclosure features: 32A 3-phase N+E 400V interlocked switch, RCD-protected socket outlets, independent emergency stop buttons for each socket, enabling localised power isolation for enhanced safety and compliance.